search-loading

TFM - Volume flow monitoring

Monitoring of fume hoods, supply air, exhaust air, suction extraction systems


Brief Description

The correct ventilation function of a fume hood must be monitored according to the applicable standards by an independent device with a guaranteed power supply. In case of a fault, an optical and acoustic alarm must be emitted. These requirements are fulfilled through the use of a TROX TFM device.

Device variant TFM-1 with integrated measurement of the volume flow being monitored

Device variant TFM-2 with 0-10 V input for recording the volume flow being monitored


  • 2 independent monitoring values

  • Individual configuration of monitoring values

  • Control panel for signaling of operating and alarm conditions

  • Integrated power fail monitoring


Information on configuration software TROX MConnect
Technical data

  • 2 independent volume flow monitoring values with upper and lower limits

  • Deactivation of the monitoring function either as break contact or make contact

  • Sash window monitoring > 500 mm with optical/acoustic alarm

  • Alarm signalling can be configured:
    Trigger delay, duration of acoustic alarm, alarm transmission per relay

  • Signalling in case of supply voltage failure

  • Supply voltage 24 V AC/DC





Device variant TFM-1
With integrated measurement of the actual volume flow value being monitored via an installed effective pressure measuring device using an effective pressure measuring lance

Scope of supply

  • Monitoring device with membrane pressure transmitter with long-term stability

  • Measuring lance and connecting tubes

  • Control panel for the signalling of operating and alarm states and the activation of additional functions

  • Optional control panel type AF-1with expanded scope of functions






Device variant TFM-2
With an analogue 0-10 V input for the recording of the actual volume flow value, e.g. from the output of a VAV controller

Scope of supply

  • Monitoring device

  • Control panel for the signalling of operating and alarm states and the activation of additional functions

  • Optional control panel type AF-1 with expanded scope of functions



Downloads Group Type Ident-No. Type / Size
         
TFM/TPM LABCONTROL-MONITORING Technical Information 7.4/3/EN/1 PDF / 469 KB 
TFM/TPM LABCONTROL-MONITORING Assembly and Operating Instruction 7.4/3/EN/1 PDF / 402 KB 
TFM control panel - User manual LABCONTROL-MONITORING Operating Manual - PDF / 42 KB 

Installation examples

Tailor-made solutions -

the air management system LABCONTROL
More installation examples

Contact

TROX Malaysia Sdn Bhd.

20 Persiaran Bunga Tanjung 1
Senawang Land Industrial Park
Tel: (+6) 06-678 8188


Contact and locations