Type FSL-B-ZAS


Decentralised sill units type FSL-B-ZAB supply the building with conditioned fresh air.

In addition to mechanical ventilation with heat recovery and air filtration equipment is guaranteed with this approach, the heating and cooling of office space.

FSL-B-ZAS
Supply and exhaust air units with secondary air function:

  • Mechanical ventilation with heat recovery
  • Façade integrated modular design:
    Base casing for installation during construction phase
    Modular inserts for subsequent fitting
  • Quasi displacement flow
  • Heat exchanger for heating and cooling
  • Supply and extract air mode, mixing with secondary (induced) air, and full secondary (recirculated) air modes are possible
  • Energy efficient radial flow fans
  • Fan speed controlled in 3 steps
  • Controlled/limited fresh air flow rate independent of wind pressure

FSL-B-ZAS
Legend

1 Extract air filter
2 Outdoor air filter
3 Air/Air-Heat recovery unit
4 Air/Water-Reheat coil
5 Supply air fan
6 Exhaust air fan
7 Back draught damper (automatic)
8 Recirculation bypass damper with spring return actuator
9 Recovery unit bypass damper with spring return actuator
10 Heating/cooling valves
11 Façade dampers exhaust air/outdoor air
12 Fresh/Intake air inlet
13 Exhaust air discharge
14 Supply air outlet
15 Extract air inlet
16 Coupled facade dampers
17 Shut-off ball valve
18 Balancing and shut-off valve
19 Extract air temperature sensor
20 Supply air temperature sensor
21 Flow rate controller
22 Frost protection thermostat
The fresh/outdoor air enters directly through an opening in the façade. There is a spring return motorised shut-off damper (11) located at the bottom of the unit in the outdoor air inlet(12), this closes the inlet when the unit is inactive or in the case of a power failure. The exhaust air damper is coupled to the outside air damper by means of a connecting shaft (16) and the system is operated by a single actuator.
The fresh air is cleaned using an F6 fine dust filter (2) and then passes through an automatic mechanical flow rate controller (21) which limits the fresh air flow rate to a set maximum. Then the air passes through a recuperative heat recovery unit (3) in which part of the heat energy from the extract air is transferred to the inlet fresh air. A radial supply fan (5) then discharges the air through a 4 pipe coil with heating and cooling capacity. The air is finally discharged into the room through an under sill slot with a displacement flow characteristic. The extract air is taken from the upper sill area then passes through a G3 coarse dust filter (1). After this the air passes through the recuperative heat recovery unit (3). When in energy saving mode, in a transitional period, or for anti icing protection, a motorised bypass damper (9) is opened which bypasses the heat recovery system (3). The exhaust air fan (6) produces the necessary pressure differentials for the extract system. The motorised shut-off damper (11) with spring return actuator closes the exhaust air outlet when the system is shut down or in the case of a power failure.
The type FSL-B-ZAU model Capricorn can provide three flow rates 60/90/120 m3/h. All three settings can operate on full recirculation or full fresh air (as described above). For full fresh air, to achieve this the BMS opens the inlet and exhaust air dampers (11) and closes the recirculation damper (8). The BMS operates the supply air and exhaust air fans in parallel at the required level.
For full recirculation the fresh air inlet and exhaust air dampers (11) are closed and the recirculation damper (8) is opened.
In this case the exhaust air fan is switched off by means of a relay and the supply air fan is operated by the BMS to provide three flow rates with full recirculation.
The units can additionally operate in an asynchronous balanced mode. To achieve this, the fresh air inlet and exhaust air dampers (11), as well as the recirculation damper (8), must be opened. In this mode a second relay which is integrated into the unit switches the exhaust air fan on, providing a constant flow rate independent of the BMS requirements, this is at speed one providing 60 m3/h. If the fan is activated from central control and operates at speeds two or three, this only effects the supply air fan. The result is that the exhaust air is at a constant flow rate of 60 m3/h and the fresh/outside air supply is at 60 m3/h and depending on the actual fan setting there is a recirculation air flow of 30 m3/h or 60 m3/h for fan speeds two and three respectively. If the minimum fresh/outdoor air is being used with fan speeds two and three this mixing operation can save substantially more energy in the heating or cooling modes than when in the full fresh air mode due to the benefits of thermal recovery.
FSL-B-ZAS
Under sill ventilation units type FSL-B-ZAS with supply and exhaust functions are used for decentralized ventilation and for heating and cooling of rooms and buildings. The devices are manufactured according to specific project-site conditions. The ventilation units type FSL-B-ZAS consist of a solid base to be integrated into the façade with exterior and exhaust air dampers placed thereon, and the functional box.
Due to the use of ventilation devices type FSL-B-ZAS arise in the inner building design architecturally great freedom.
The integration of technology is possible with a minimal space requirement of only 200 mm lights installation depth.
This is particularly important for buildings with full-height glazing and traditional technology areas where it accounts.

 

Downloads Group Type Ident-No. Type / Size
         
CAPRICORN HOUSE - Decentralised sill ventilation units FSL-B-ZAU Wall Ventilation Units Project Information PI/FSL/11/EN/2 PDF / 248 KB 

Reference

Distrito de la Comunicación de Telefónica

More than 30,000 TROX chilled beams of DID300B type
Reference

Contact

TROX Malaysia Sdn Bhd.

20 Persiaran Bunga Tanjung 1
Senawang Land Industrial Park
Tel: (+6) 06-678 8188
Contact and locations